Battery Backup


 

  • Battery Backup consists of two 12V/75Ah Sealed Lead-Acid Batteries connected in series for 24V operation.

  • Provides 24-hour battery backup for our BDAs under full load. This is calculated with 70% derated battery capacity.

  • Batteries are enclosed in a steel, NEMA3R type vented enclosure with red powder-coat finish.

  • Optional Seismic Kit is available

  • Mounting Tabs Spacing matched the BDA so that both can be installed on the same strut.

  • Requires 14AWG or larger wire with an in-line fuse connected to the positive terminal for connection to the BDA.